
Navigating Title 24: 2025 Commercial Window and Glazing Requirements
If you are building or remodeling a commercial building in California, the windows, storefront, curtain wall and skylights have to meet the state's energy code: Title 24, Part 6, the Building Energy Efficiency Standards. The 2025 edition now applies to most projects, and it added new rules that matter to glazing, including a new mandatory limit on the average window U-factor and a vestibule requirement at many public entrances.
At Ramos Industries, Inc., we work with architects, general contractors and energy consultants to match glass and framing to the energy code. This guide covers the current numbers and section references so you can plan around them early.
Last reviewed November 2026 against the 2025 Building Energy Efficiency Standards (CEC-400-2025-010). The energy consultant's compliance documents and the local building department have the final word on a specific project.

Which edition applies
The California Energy Commission adopted the 2025 Energy Code on September 11, 2024. Buildings whose permit applications are submitted on or after January 1, 2026 must comply with it. Projects whose permit application was received on or before December 31, 2025 stay under the 2022 code. The code is updated on a three-year cycle.
What Title 24 measures on glazing
Title 24 regulates the whole rated window or wall product, not just the glass. Every fenestration product must be rated, or must use the code's default values (Section 110.6):
- U-factor (how much heat flows through), rated to NFRC 100. Lower is better.
- Solar heat gain coefficient, SHGC (how much solar heat gets in), rated to NFRC 200. The prescriptive tables use "relative SHGC" (RSHGC), which can give credit for overhangs.
- Visible transmittance, VT (how much daylight gets in), rated to NFRC 200 or ASTM E972. Higher is better.
- Air leakage. Manufactured windows must leak no more than 0.3 cfm per square foot, and nonresidential single doors 0.3 and double swinging doors 1.0 cfm per square foot, tested to NFRC 400 or ASTM E283 at 75 pascals (110.6(a)1).
The 2025 numbers for new commercial buildings
A new mandatory cap (Section 120.7(d)). New for 2025: vertical fenestration in nonresidential and hotel/motel buildings must have an area-weighted average U-factor no higher than 0.47, no matter which compliance path is used. There is an exception for buildings in Fire Hazard Severity Zones or Wildland-Urban Interface areas that meet the wildfire building rules.
Prescriptive path (Section 140.3 and Table 140.3-B). If the project uses the prescriptive path, vertical glazing must meet these area-weighted values for nonresidential buildings:
| Product type | Max U-factor | Max RSHGC | Min VT |
|---|---|---|---|
| Curtain wall or storefront | 0.41 (0.38 in Climate Zones 1 and 7) | 0.26 (0.25 in Zones 1 and 7) | 0.46 |
| Fixed window | 0.36 (0.34 in Zones 9 and 11 to 15) | 0.25 (0.22 in Zones 9 and 11 to 15) | 0.42 |
| Operable window | 0.46 | 0.22 | 0.32 |
| Glazed doors | 0.45 | 0.23 | 0.17 |
Other prescriptive limits:
- Window area. Total window area no more than 40 percent of the gross exterior wall area, and west-facing window area no more than 40 percent of the west wall, or 6 feet times the display perimeter if that is larger (140.3(a)5A).
- Display windows. First-floor display perimeter windows can use an RSHGC up to 0.56 where codes restrict overhangs (140.3(a)5C, Exception 1).
- Skylights. No more than 5 percent of the roof area (10 percent for atria over 55 feet high). Glass skylights: U-factor 0.58 curb-mounted or 0.46 deck-mounted, SHGC 0.25, VT 0.49 (140.3(a)6 and Table 140.3-B).
Hotel/motel guest rooms (Table 140.3-C) and multifamily buildings (Section 170.2) have their own requirements.
Performance path. If the design cannot meet the prescriptive values, for example a glass-heavy facade over the 40 percent window limit, the energy consultant can model the whole building and trade glazing against other systems. The 0.47 mandatory cap still applies.
Which climate zone are you in? Southern California projects can land in several zones, from coastal Zones 6 and 7 to inland Zones 8, 9 and 10 and desert Zones 14 and 15. Look up the exact address with the Energy Commission's climate zone tool before picking glass.
Aluminum windows and storefront: why the NFRC rating matters
Commercial storefront, curtain wall and atrium roof systems are "site-built" fenestration under Title 24: factory-made parts assembled at the job site. Products that are not NFRC-rated must use the code's default values, and those defaults are high. Table 110.6-A lists a default U-factor of 0.71 for a double-pane fixed window in a metal frame without a thermal break, and 0.55 with a thermal break. Both are above the new 0.47 mandatory cap and well above the prescriptive values in the table above. In practice, that means new commercial aluminum glazing needs real NFRC ratings for the framed product, glass and frame together, to show compliance. Thermally broken framing and low-E insulating glass are the usual tools to get there. For more on framing, see Thermal-Break vs. Non-Thermal Aluminum Framing.
Labels, certificates and acceptance
- Manufactured windows and doors carry a temporary label with U-factor, SHGC and VT that must stay on until the inspector sees it, plus a permanent label (110.6(a)5 and Title 24 Part 1, Section 10-111).
- Site-built systems (storefront and curtain wall) rated by NFRC use an NFRC label certificate instead of a sticker on each unit (10-111(a)). Unrated site-built products carry a temporary label with "CEC Default" U-factor, SHGC and VT values instead (10-111(a)1B ii).
- Acceptance before occupancy. For site-built fenestration in buildings other than single-family homes, a certificate of acceptance confirming that the installed products match the label certificate must be completed, signed and submitted before the occupancy permit is granted, and the label certificate must be available at the project (110.6(a)6 and Reference Nonresidential Appendix NA7).
- NFRC program change in 2026. The 2025 code text refers to NFRC's Component Modeling Approach (CMA) label certificates. NFRC retired its Component Modeling Approach (CMA) program on May 29, 2026 and moved commercial products to a new program, NFRC 715. NFRC has also announced the end of its site-built certification route. Ask your glazing contractor early which NFRC certification the system will carry, and confirm what the plan checker will accept.
New in 2025: vestibules at public entrances
Section 120.7(e) now requires an enclosed vestibule at public entrances of newly constructed Group A, B, E, I and M buildings (assembly, business, education, institutional and mercantile). Doors into and out of the vestibule need self-closers, and the vestibule must work so both sets of doors do not have to be open at once. There are exceptions, including doors that open from a space under 3,000 square feet, entrances with a tested air curtain, and buildings in Climate Zones 2 to 13 that are under four stories and under 10,000 square feet of conditioned floor area. If a vestibule is required, it changes the storefront entrance layout, so it belongs in early design.

Replacing or adding windows in an existing building
The old rule of thumb that "anything over 25 square feet triggers Title 24" is not in the code. For nonresidential and hotel/motel buildings, any window replacement that is not a repair is an alteration under Section 141.0(b), no matter how small. The square footage only decides which extra limits apply:

- Any replacement, any size: on the prescriptive path, the replaced windows must meet the U-factor in Table 141.0-A: 0.47 in most climate zones, 0.58 in Zones 3 and 5.
- Replacing more than 150 square feet of the building's vertical windows: two more limits apply. The replaced units have a mandatory U-factor cap of 0.58 (141.0(b)1E), and on the prescriptive path they must also meet the Table 141.0-A RSHGC (0.31 in most climate zones, 0.41 in Zones 1, 3, 5 and 16) and VT from Table 140.3-B.
- Replacing 150 square feet or less: the Table 141.0-A U-factor still applies, but the RSHGC and VT limits do not (141.0(b)2A, Exception 1).
- Adding more than 50 square feet of new window area: the added glazing must meet the 0.47 cap (141.0(b)1E and 120.7(d)), and on the prescriptive path it must meet Table 140.3-B. Adding 50 square feet or less skips the RSHGC and VT limits.
- Replacing only the glass in an existing frame, or a sash in an existing frame, counts as a repair. The replacement must perform at least as well as the original (141.0(b)2A note and 141.0(c)).
Note that the default U-factor for a non-thermally broken metal fixed window (0.71) is above the 0.58 alteration cap, while the thermally broken default (0.55) is under that cap but still above the 0.47 that Table 141.0-A sets in most climate zones on the prescriptive path.
Arizona projects
Title 24 is a California code. Arizona has no statewide building code for private commercial buildings, so energy rules for glazing depend on what each city has adopted.
Planning checklist
- Look up the climate zone and decide early between the prescriptive and performance paths.
- Check the window-to-wall ratio against the 40 percent prescriptive limit.
- Specify the framed product's NFRC U-factor, SHGC and VT, not just the glass data.
- Confirm the system's NFRC certification path for site-built storefront and curtain wall.
- Check whether the entrances need a vestibule under 120.7(e).
- On remodels, total up how many square feet of windows are being replaced or added.
- Plan for the fenestration acceptance certificate before occupancy.
How Ramos Industries helps
Ramos Industries, Inc. is a commercial glazing contractor serving Southern California and Arizona (CA C-17 #1034872, AZ ROC #343677). On Title 24 projects we:
- Review the energy consultant's compliance documents and the glazing spec for product type, U-factor, SHGC and VT
- Propose glass and framing options that meet the numbers for the project's climate zone
- Provide submittals with NFRC ratings and label certificate documentation
- Install storefront, curtain wall, window wall and replacement glazing to match what was approved
The energy consultant and the building department make the compliance call; our part is to make sure the products bid, submitted and installed line up with it.
Planning a California commercial project?
Bring us in before the glass is specified and we will help you compare options that meet Title 24 for your climate zone. Contact Ramos Industries to talk through your project.
Related reading: 2025-2026 California Energy Code Changes Affecting Glazing, Value-Engineering Glass Without Failing Title 24 and Understanding Low-E Glass in Commercial Glazing.
Frequently Asked Questions
Buildings whose permit applications are submitted on or after January 1, 2026 must comply with the 2025 Energy Code. Projects whose application was received on or before December 31, 2025 stay under the 2022 code.
The vertical windows in a new nonresidential or hotel/motel building must have an area-weighted average U-factor of 0.47 or lower (Section 120.7(d)). On the prescriptive path the limits are tighter, for example 0.41 for curtain wall and storefront and 0.36 for fixed windows in most climate zones (Table 140.3-B).
Yes, unless the work is only a repair. Any window replacement is an alteration under Section 141.0(b), whatever its size. On the prescriptive path, replaced windows must meet the U-factor in Table 141.0-A (0.47 in most climate zones, 0.58 in Zones 3 and 5). If more than 150 square feet of the building's vertical windows are replaced, a mandatory 0.58 cap also applies and the RSHGC and VT limits kick in. Adding more than 50 square feet of new windows requires 0.47 or lower. Replacing just the glass in an existing frame is treated as a repair.
In practice, yes. Unrated products must use the code's default values, and the default U-factor for a double-pane metal fixed window is 0.71 without a thermal break and 0.55 with one, both above the 0.47 mandatory cap for new buildings. Site-built systems rated by NFRC use an NFRC label certificate rather than a sticker on each unit; unrated site-built systems carry a temporary label with "CEC Default" values.
For many new buildings, yes. Section 120.7(e) requires an enclosed vestibule at public entrances of new Group A, B, E, I and M buildings, with exceptions such as entrances from spaces under 3,000 square feet, tested air curtains, and smaller buildings in Climate Zones 2 to 13.
Related Services
Energy Efficient Glass
Low-E, insulated, and solar control glazing solutions that reduce energy costs and meet Title 24 requirements.
Storefronts
Aluminum storefront systems for retail, restaurants, banks, and commercial entries. New construction and tenant improvement scopes with low e glass options.
Curtain Wall
Aluminum curtain wall systems for commercial new construction, including stick built and unitized assemblies with insulated low e glazing.
Window Wall
Aluminum window wall systems for commercial and multifamily new construction, sitting on the floor slab and integrating with the building structure.
Glass Replacement & Repair
Full service commercial glass replacement for windows, storefronts, and curtain wall systems, including expert substrate and color matching so repairs blend seamlessly with existing glazing.
Related Articles

Commercial Facade and Glazing Trends for 2026
The 2026 commercial facade trends GCs and architects need: unitized curtain wall, thermal-break upgrades, Title 24 performance, and dynamic glass.

Commercial Glazing Lead Times in SoCal by System (2026)
2026 commercial glazing lead times in Southern California by system, storefront, curtain wall, unitized, IGUs, and specialty glass, plus what drives delays.

The Complete Guide to Commercial Glass Replacement and Retrofits
Everything you need to know about replacing glass in an existing commercial building. Covers when to replace vs. repair, retrofit options, energy upgrade incentives, and how to minimize tenant disruption.